|

Fire Alarm Servicing, Fire Alarm Maintenance System
Scheduled
Maintenance of Fire Alarm Systems.
Servicing
of fire detection and alarm system should be carried out at three monthly
intervals. This is recommended in the British Standard Code of Practice
(BS 5839 and BS 5306). On each service visit the following work should
be carried out:
- Contact
Site Manager on arrival
- Isolate
Brigade/Central Station link - if applicable *
- Isolate
sounders on client's instructions only *
- Isolate
all output shutdown relays - as applicable including any extinguishant
trigger *
- Isolate
any links, which interlink to other systems i.e. building management
alarms. *
- Inspect
and test the batteries for correct voltage and standby capacity and
charge. Batteries will be replaced at the end of the manufacturer's
specified shelf life in accordance with BS 5839 Part 1, 1988
- Test
the operation of the indicator panel, replace lamps where necessary.
Clean panel front
- Test
and clean 25% of all smoke detectors, where less than 10 test 100% each
visit.
- Visually
inspect heat detectors for damage or other conditions such as a heavy
coat of paint likely to impair their correct operation. Routine tests
of operation of heat detectors should be carried out to confirm their
correct operation. Wipe clean all devices.
- Inspect
and test 25% of all manual call points, where less than 10 test 100%
each visit.
- Check,
where applicable, door release units for correct operation
- Check,
where applicable any extension indicator lights.
- Test
the external audible alarm where fitted to the system and test all other
connected alarms.
- Inspect
all panel termination and printed circuit boards for condition.
- Test
at least once a year (with Clients authority) all outputs and extinguishant
actuator (electro/mechanical type only)
- If applicable,
test the connection to the fire brigade and the correct operation of
the receiving panel.
- Enter
details of the service into site log book
- Carry
out inspection of all areas of premises, furnishings and equipment there
in and highlight recommendations to maintain/improve efficiency of the
system.
- Reinstate
items marked '*'
- Leave
with Site Manager after each service a test report as required under
the British Standard Code of Practice. If faults have been noted, enter
on certificate.
|